BMS(电池堆)通信状态 R uint16 "0:正常
|
|||
|
|
1:故障" bit位从低到高分别对应1~16 0x2001
|
|||
|
|
BCU(电池簇)通信状态 R uint64 "0:正常
|
|||
|
|
1:故障" bit位从低到高分别对应1~64 0x2002
|
|||
|
|
PCU(主控)通信状态 R uint16 "0:正常
|
|||
|
|
1:故障" bit位从低到高分别对应1~16 0x2006
|
|||
|
|
PCS(模块)通信状态 R uint64 "0:正常
|
|||
|
|
1:故障" bit位从低到高分别对应1~64 0x2007
|
|||
|
|
电表总接点通信状态 R uint16 "0:正常
|
|||
|
|
1:故障" bit位从低到高分别对应1~16 0x200B
|
|||
|
|
电表通信状态 R uint32 "0:正常
|
|||
|
|
1:故障" bit位从低到高分别对应1~32 0x200C
|
|||
|
|
消防通信状态 R uint16 "0:正常
|
|||
|
|
1:故障" bit位从低到高分别对应1~16 0x200E
|
|||
|
|
UPS通信状态 R uint16 "0:正常
|
|||
|
|
1:故障" bit位从低到高分别对应1~16 0x200F
|
|||
|
|
温湿度总接点通信状态 R uint16 "0:正常
|
|||
|
|
1:故障" bit位从低到高分别对应1~16 0x2010
|
|||
|
|
温湿度通信状态 R uint32 "0:正常
|
|||
|
|
1:故障" bit位从低到高分别对应1~32 0x2011
|
|||
|
|
空调总接点通信状态 R uint16 "0:正常
|
|||
|
|
1:故障" bit位从低到高分别对应1~16 0x2013
|
|||
|
|
空调通信状态 R uint32 "0:正常
|
|||
|
|
1:故障" bit位从低到高分别对应1~32 0x2014
|
|||
|
|
控制干接点(配电系统)状态 R uint16 "0:开路
|
|||
|
|
1:闭合" bit位从低到高分别对应1~16 0x2016
|
|||
|
|
状态干接点(配电系统)状态 R uint16 "0:开路
|
|||
|
|
1:闭合" bit位从低到高分别对应1~16 0x2017
|
|||
|
|
BCU总通信状态 R uint16 0:正常 1:告警 2:故障 0x2018
|
|||
|
|
PCU总通信状态 R uint16 0:正常 1:告警 2:故障 0x2019
|
|||
|
|
电表总通信状态 R uint16 0:正常 1:告警 2:故障 0x201A
|
|||
|
|
消防总通信状态 R uint16 0:正常 1:告警 2:故障 0x201B
|
|||
|
|
UPS总通信状态 R uint16 0:正常 1:告警 2:故障 0x201C
|
|||
|
|
温湿度总通信状态 R uint16 0:正常 1:告警 2:故障 0x201D
|
|||
|
|
空调总通信状态 R uint16 0:正常 1:告警 2:故障 0x201E
|
|||
|
|
EMU通信状态 R uint16 0:正常 1:告警 2:故障 0x201F
|
|||
|
|
冷机总通信状态 R uint16 0:正常 1:告警 2:故障 0x2020
|
|||
|
|
冷机总接点通信状态 R uint16 "0:正常
|
|||
|
|
1:故障" bit位从低到高分别对应1~16 0x2021
|
|||
|
|
冷机通信状态 R uint16 "0:正常
|
|||
|
|
1:故障" bit位从低到高分别对应1~16 0x2022
|
|||
|
|
预留 0x2023~0x2079
|
|||
|
|
预留
|
|||
|
|
判断总表的三相总有功 < -5.0fkW 充电 >5.0fkW放电 否则停机 R uint16 0:充电 1:放电 2:停机 储能状态 0x207A
|